Installation
Installation
The device is not dependent on location or position. The device is designed to fit on 35mm DINÂ rails (EN 50022) or to be installed with a front installation frame. To remove the meter from a DIN Ârail just pull the spring loaded bolt on the underside.
The cabling for the current transformer should be held as short as possible. In case of significant measurement errors after Installation, please consider the following points:
The use of Rogowski Âcoils as current transformers for the converter counter is discouraged because of the multiple current / voltage transformation and external amplifiers. Each transformation adds a multiplicative error on the measurement.
Energy Direction (current transformer) : If all currents are expected to be positive (import measurement) but one or several currents are negative, please check the correct installation of your current transformers as they have been wrongfully installed.
Transformer Ratio (current transformer) : The transformer ratios on the meter must be the same as the ones of the installed current / voltage transformers.
Correct Phase assignment: Current L1 and Voltage L1 must be connected to the same measurement system. See Connection Diagram.
Make sure that all connected wires are voltage free before you install / change or check the meter. Touching any live elements is dangerous to life!
The CT models have voltage on the current paths! Make sure that the voltage connections are voltage free before you install the current transformer. Touching any live elements is dangerous to life!
The installation of the meter must be carried out by qualified and trained personnel. Current transformers must not operate open loop as high voltages can occur. These voltages can lead to substantial personal and/or property damage.
Nonobservance of mounting and installation instructions may lead to damage or destruction of this meter.