📖
EM4302T-LRW
  • Introduction
  • About this document
  • Declaration of Conformity
  • DEVICE
    • Device Overview
      • Installation
      • Connection Diagrams
      • Wiring and Torques
    • Technical Specifications
    • Operation Guide
      • 🔡Parameters and Settings
        • Communication Settings
    • Registers
      • Generic Data
      • Device Data
      • LoRaWAN Data
  • LoRaWAN
    • LoRaWAN Communication
      • Payloads
        • Uplinks
        • Downlinks
  • Support and Maintenance
    • Troubleshooting
    • Maintenance
    • Changelog
Powered by GitBook
On this page
  • Holding Registers
  • Preset Multiple Registers
  • Alarms
  1. DEVICE
  2. Registers

Device Data

Holding Registers

The following table shows the holding registers (03H) available through the devices communication protocol.

Description
Length
Data Format
Units
High Byte
Low Byte

Phase 1 line to neutral volts.

4

ULONG

0.01V

00

00

Phase 2 line to neutral volts.

4

ULONG

0.01V

00

02

Phase 3 line to neutral volts.

4

ULONG

0.01V

00

04

Phase 1 current.

4

ULONG

0.001A

00

06

Phase 2 current.

4

ULONG

0.001A

00

08

Phase 3 current.

4

ULONG

0.001A

00

0A

Phase 1 active power.

4

LONG

0.001kW

00

0C

Phase 2 active power.

4

LONG

0.001kW

00

0E

Phase 3 active power.

4

LONG

0.001kW

00

10

Phase 1 reactive power.

4

LONG

0.001kvar

00

12

Phase 2 reactive power.

4

LONG

0.001kvar

00

14

Phase 3 reactive power.

4

LONG

0.001kvar

00

16

Phase 1 apparent power.

4

ULONG

0.001kVA

00

18

Phase 2 apparent power.

4

ULONG

0.001kVA

00

1A

Phase 3 apparent power.

4

ULONG

0.001kVA

00

1C

Phase 1 power factor (1).

2

INT

0.001

00

1E

Phase 2 power factor (1).

2

INT

0.001

00

1F

Phase 3 power factor (1).

2

INT

0.001

00

20

Phase 1 phase angle.

2

INT

0.01°

00

21

Phase 2 phase angle.

2

INT

0.01°

00

22

Phase 3 phase angle.

2

INT

0.01°

00

23

Line 1 to Line 2 volts.

4

ULONG

0.01V

00

24

Line 2 to Line 3 volts.

4

ULONG

0.01V

00

26

Line 3 to Line 1 volts.

4

ULONG

0.01V

00

28

Frequency of supply voltages.

2

UINT

0.01Hz

00

2A

Total system active power.

4

LONG

0.001kW

00

2C

Total system reactive power.

4

LONG

0.001kvar

00

2E

Total system apparent power.

4

LONG

0.001kVA

00

30

Total system power factor (1).

2

INT

0.001

00

32

Total system phase angle.

2

INT

0.01°

00

33

Sum of line currents.

4

ULONG

0.001A

00

34

Average line to neutral volts.

4

ULONG

0.01V

00

36

Average line to line volts.

4

ULONG

0.01V

00

38

Average line current.

4

ULONG

0.001A

00

3A

Neutral current.

4

ULONG

0.001A

00

3C

Total system active power demand (3).

4

LONG

0.001kW

00

66

Total system reactive power demand (3).

4

LONG

0.001kvar

00

68

Total system apparent power demand.

4

LONG

0.001kVA

00

6A

Phase 1 current demand.

4

ULONG

0.001A

00

6C

Phase 2 current demand.

4

ULONG

0.001A

00

6E

Phase 3 current demand.

4

ULONG

0.001A

00

70

Maximum total system active power demand (3).

4

LONG

0.001kW

00

7C

Maximum total system reactive power demand (3).

4

LONG

0.001kvar

00

7E

Maximum total system apparent power demand.

4

ULONG

0.001kVA

00

80

Maximum phase 1 current demand.

4

ULONG

0.001A

00

82

Maximum phase 2 current demand.

4

ULONG

0.001A

00

84

Maximum phase 3 current demand.

4

ULONG

0.001A

00

86

Total import active energy.

4

ULONG

0.01kWh

04

00

Total export active energy.

4

ULONG

0.01kWh

04

02

Total active Energy.

4

ULONG

0.01kWh

04

04

Total import reactive energy.

4

ULONG

0.01kvarh

04

08

Total export reactive energy.

4

ULONG

0.01kvarh

04

0A

Total reactive Energy.

4

ULONG

0.01kvarh

04

0C

Total active energy of rate 1

4

ULONG

0.01kWh

04

38

Total active energy of rate 2

4

ULONG

0.01kWh

04

3A

Total active energy of rate 3

4

ULONG

0.01kWh

04

3C

Total active energy of rate 4

4

ULONG

0.01kWh

04

3E

Import active energy of rate 1

4

ULONG

0.01kWh

04

40

Import active energy of rate 2

4

ULONG

0.01kWh

04

42

Import active energy of rate 3

4

ULONG

0.01kWh

04

44

Import active energy of rate 4

4

ULONG

0.01kWh

04

46

Export active energy of rate 1

4

ULONG

0.01kWh

04

48

Export active energy of rate 2

4

ULONG

0.01kWh

04

4A

Export active energy of rate 3

4

ULONG

0.01kWh

04

4C

Export active energy of rate 4

4

ULONG

0.01kWh

04

4E

Total reactive energy of rate 1

4

ULONG

0.01kvarh

04

50

Total reactive energy of rate 2

4

ULONG

0.01kvarh

04

52

Total reactive energy of rate 3

4

ULONG

0.01kvarh

04

54

Total reactive energy of rate 4

4

ULONG

0.01kvarh

04

56

Import reactive energy of rate 1

4

ULONG

0.01kvarh

04

58

Import reactive energy of rate 2

4

ULONG

0.01kvarh

04

5A

Import reactive energy of rate 3

4

ULONG

0.01kvarh

04

5C

Import reactive energy of rate 4

4

ULONG

0.01kvarh

04

5E

Export reactive energy of rate 1

4

ULONG

0.01kvarh

04

60

Export reactive energy of rate 2

4

ULONG

0.01kvarh

04

62

Export reactive energy of rate 3

4

ULONG

0.01kvarh

04

64

Export reactive energy of rate 4

4

ULONG

0.01kvarh

04

66

Preset Multiple Registers

Parameter
Description
Length (bytes)
Data Format
High Byte
Low Byte
R/W

Key Parameter Programming Authorization (KPPA)

Read: to get the status of the KPPA

0 = not authorized;1 = authorized

Write the correct password to get KPPA, enable to program key parameters.

2

UINT

50

00

R/W

Demand Period

Write demand period: 0~60 minutes, Default 60.

Range: 0~60, 0 means function update every second.

2

UINT

50

02

R/W

Slide time

Default 1, min.

Range:1 ~ (Demand Period -1).

2

UINT

50

03

R/W

Modbus address

Write the modbus address

Range: 1 to 247 for MODBUS Protocol, default 1.

2

UINT

50

05

R/W

Network Baud Rate

Write the network port baud rate for MODBUS Protocol, where:

0 = 1200 baud.

1 = 2400 baud.

2 = 4800 baud.

3 = 9600 baud, default.

2

UINT

50

06

R/W

Parity and stop bit

Write the network port parity/stop bits for MODBUS Protocol, where:

0 = One stop bit and no parity, default.

1 = One stop bit and even parity.

2 = One stop bit and odd parity.

3 = Two stop bits and no parity.

2

UINT

50

07

R/W

Password

Read: to get the password of the meter

Write: to program the new password of the meter

Default : 0000

(KPPA is asked)

2

UINT

50

08

R/W

Pulse 1 Energy Type

Write MODBUS Protocol

input parameter for pulse

output 1:

1: import active energy

2: total active energy

4: export active energy, default

5: import reactive energy

6: total reactive energy

8: export reactive energy

2

UINT

50

09

R/W

Pulse 1 constant

Write pulse constant index: n

= 0 to 3

0 : 1000 imp/kWh(kvarh), default

1 : 100 imp/kWh(kvarh)

2 : 10 imp/kWh(kvarh)

3 : 1 imp/kWh(kvarh)

Note: When the pulse constant is set to 1000 imp, the pulse output width is automatically modify to 35ms.

2

UINT

50

0A

R/W

Pulse 1 Width

Write pulse on period in milliseconds: 60, 100 or 200, default 100.

Note: When the pulse constant is set to 1000 imp, the pulse output width is automatically modify to 35ms, which cannot be setting.

2

UINT

50

0B

R/W

Automatic Scroll Display Time

Automatic scroll display time, unit : second

Range 0~60,default : 0

Note: 0 mean stop automatic scroll display

2

UINT

50

18

R/W

Backlit time

Backlit time, unit : minute.

Default 60.

Range 0~120 or 255,0 means backlit always on,255 means backlit always off.

2

UINT

50

19

R/W

System time

Data definition:

20-Year-Month-Date-Week-Hour-Minute-Second

8

BCD

50

1A

R/W

Tariff

Data definition:

Tariff number-Min-Hour

Tariff number:00,01,02,03,04;00 mean invalid tariff number

Min:00-59

Hour:00-23

24

BCD

50

1E

R/W

Alarm object(1)

Range: 0~31,and 255;

Default: 255 = null

2

UINT

51

80

R/W

Alarm action delay time

Alarm action delay time,unit: ms

Range:0~9999;default: 0 ms

Note:

When an alarm event occurs, the alarm action will be performed only after the delay time. If the delay time is set to 0, the alarm action will be executed immediately.

2

UINT

51

81

R/W

Alarm threshold (2)

The factor for the alarm threshold value is 0.001.

Example: If you need to set the alarm threshold value to 10.123, the actual value written to the register is 10123.

(10123 * 0.001 = 10.123)

4

LONG

51

82

R/W

Reset historical data

0 = reset max. demand

5 = reset SOE information

7 = reset relay control record

8 = reset daily energy consumption

9 = reset monthly energy consumption

(KPPA is asked)

2

UINT

56

00

W

Meter code

The code of the meter

2

HEX

56

01

R

Serial number

The serial number of the meter

4

ULONG

56

02

R

Software version number

Software version number : XX.YY

Data definition : The first byte represents XX, and the second byte represents YY

2

HEX

56

04

R

Hardware version number

Hardware version number : XX.YY

Data definition : The first byte represents XX, and the second byte represents YY

2

HEX

56

05

R

Alarms

tbd

PreviousGeneric DataNextLoRaWAN Data

Last updated 6 months ago