πDevice Overview
The SD-1001 is used to detect or report smoke, in order to warn people in private living areas acoustically and visually
Introduction
The Yobiiq SD1001 device is a ready-to-use smoke detector for indoor usage.
The device issues data periodically, alarms (absence of mains power, button operations, smoke detection) are send immediately after occurence.
The user can access the configuration remotely via LoRaWAN downlinks.
The SD-1001 device requires a 230V/50Hz mains connection when BLE is required.
The SD-1001 device is compatible with the IQ Platform and Application.
π The SD-1001 device is delivered by default with the OTAA join procedure so the user can connect the device to a LoRaWAN operator of choice.
Smoke alarms should not be covered, wallpapered or painted over. It is also important to pay attention to the correct installation location. Make sure to follow the instructions in this User Manual to ensure proper operation.
Residents should be aware of the escape routes in case of a fire and should familiarize themselves with them. Make sure that escape routes are accessible, and acces is not blocked.
In case of a fire, before opening a door check the door handle if it feels hot there might be a fire behind the door, leave the door closed and look for another escape route. Opening a door can add oxygen to the fire causing it to further ignite!
In case of a fire, do not waste time collecting personal items they can be replaced, your life can't. All residents should leave the building as quickly and safely as possible.
Features
Below is a list of the most common features, for more details check the operational overview.
85dB buzzer: The buzzer generates a sound pattern of at least 85dB.
230V mains or battery operated: The SD-1001 can operate on a 230V mains power supply with the battery as backup, or only on the battery as power supply.
Wired Interconnect: The SD-1001 can be interconnected to up to 48 smoke detectors by wire.
Wireless Interconnect: Wireless interconnection is possible for up to 24 smoke detectors, for this a local additional gateway is required.
Hush/Silence: The SD-1001 can be put into a hush/silence mode by pressing the button locally.
LED Status: LED indication for Power, LoRaWAN Network Status and Battery Status.
Package contents
The device is delivered in a carton package containing the following:
The SD-1001 Smoke Detector
Dust Cap
Screw and Plug
Quick Start Manual
Warning / Operation Manual for users
Dimensions
Values are in millimeters
Instructions for correct assembly
Your Smoke Detector package will always contain a document with instructions for correct assembly, this document should always be followed when installating the Smoke Detector.
Recommended Locations
The guidelines below are recommendations, you should always follow local standards and laws when installing smoke detectors!
Locate the first alarm in the immediate area of the sleeping rooms. Try to monitor the exit path as the sleeping rooms are usually farthest from the exit. If more than one sleeping area exists, locate additional alarms in each sleeping area.
Locate additional alarms to monitor any stairway as stairways act like chimneys for smoke and heat.
Locate at least one alarm on every floor level.
Locate an alarm in every sleeping room.
Locate an alarm in every room where electrical appliances are operated (i.e. portable heaters or humidifiers).
Locate an alarm in every room where someone sleeps with the door closed. The closed door may prevent an alarm not located in that room from waking the sleeper.
Smoke, heat, and combustion products rise to the ceiling and spread horizontally. Mounting the smoke alarm on the ceiling in the center of the room places it closest to all points in the room. Ceiling mounting is preferred in ordinary residential construction.
When mounting an alarm on the ceiling, locate it at a minimum of 10 cm from the side wall. (see Figure 1).
When mounting the alarm on the wall, use an inside wall with the top edge of the alarm at a minimum of 10 cm and a maximum of 40 cm below the ceiling. (see Image 1).
In homes that are not well insulated, extreme heat or cold can be transferred from the outside to the inside through poorly insulated walls and roof. This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling. If you are not sure about the insulation in your home, or if you notice that the outer walls and ceiling are either hot or cold, install the alarm on an inside wall. In such homes, install the smoke alarm with the top edge of the alarm at a minimum of 10 cm and a maximum of 40 cm below the ceiling (see Image 1).
Put smoke alarms at both ends of a bedroom hallway or large room if the hallway or room is more than 10 m long.
Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 0.9 m of the highest point (measured horizontally). Smoke alarms in rooms with ceiling slopes greater than .3 m in 2.4 m horizontally shall be located on the high side of the room. A row of detectors shall be spaced and located within 0.9 m of the peak of the ceiling measured horizontally (see Image 3).
Install Smoke Alarms on tray-shaped ceilings (coffered ceilings) on the highest portion of the ceiling or on the sloped portion of the ceiling within 305mm vertically down from the highest point (see Image 3).
Locations to avoid
In the garage. Products of combustion are present when you start your motor vehicle.
Less than 10 cm from the peak of an βAβ frame type ceiling.
In an area where the temperature may fall below 0ΒΊC or rise above 40ΒΊC , such as garages and unfinished attics; this should include electrical boxes exposed to these environments.
In dusty areas. Dust particles may cause nuisance alarm or failure to alarm.
In very humid areas. Moisture or steam can cause nuisance alarms.
In areas where the Relative Humidity (RH) is above 90%.
In insect-infested areas.
Smoke alarms should not be installed within 90 cm of the following:
the door to a kitchen, the door to a bathroom containing a tub or shower.
forced air supply ducts used for heating or cooling, ceiling or whole house ventilating fans, or other high air flowareas.
Kitchens. Normal cooking may cause nuisance alarms.
Near fluorescent lights. Electronic βnoiseβ may cause nuisance alarms.
Installation
After selecting the proper smoke alarm location as described above;
Strip off the wires according to image x
Connect the wires to the correct terminals on the detector base and ensure that the terminal screws are fully tightened.
Close the terminal flap cover to avoid contact with the live terminals and risk of electric shock in case of carelessness.
Attach the detector base to the ceiling or wall. Use the screws and wall plugs provided to secure the detector base.
Close the smoke alarm base after installing a battery or removing the battery cover. Note: the detector base will only close if a battery is present. Do not attempt to close the detector base unless a battery is installed!
Power on mains and check that the Green LED lights up to indicate Main Power present.
Always use insulated wiring as per your local regulation, supported diameter is between 0,75mm2 and 2,5mm2
When testing the alarm, always keep a safe distance to the device. The detector is equiped with a loud alarm (~90 dB)
Installation is not complete until both LEDs are functioning correctly and the alarm has been checked for correct operation.
iQ Compatibility
The device is compatible with the Yobiiq iQ platform, but is also compatible with most well known data integration platforms and network servers.
The Yobiiq iQ platform is a device management service that allows you to set up your own global IoT solution.
With the iQ platform you are able to:
Monitor the health of your equipment park: battery life, reception/non-reception and the quality of the radio link.
Control the use of your equipment park: subscription and radio regulations.
Act on your equipment park: simulate service life and change configuration remotely.
Technical Specifications
General Characteristics
Last updated